Background Image
Previous Page  152 / 164 Next Page
Information
Show Menu
Previous Page 152 / 164 Next Page
Page Background

148

Current Clamps

i5s

i200

i200s

i400

i400s

Nominal current range(s)

5 A

200 A

20 A

200 A

400 A

40 A

400 A

Continuous AC current range

0.01 A - 6 A

0.5 A - 200 A

0.1 - 24 A

0.5 A - 200 A

5 A - 400 A

0.5 - 40 A

5 A - 400 A

Highest current

70 A

240 A

240 A

1000 A

1000 A

Lowest measurable current

10 mA

0.5 A

0.5 A

1 A

0.5 A

Basic accuracy (48-65 Hz)

1)

1%

1% + 0.5 A

1.5% + 0.5 A

2% + 0.15

2% + 0.15

Useable frequency

40 Hz - 5kHz

40 Hz - 10 kHz

40 Hz - 10 kHz

45 Hz - 3 kHz

45 Hz - 3 kHz

Max. working voltage

600V AC

600V AC

600V AC

1000V

1000V

Maximum conductor diameter

15 mm

20 mm

20 mm

32 mm

32 mm

Output level(s)

400 mV/A

1 mA/A

100 mV/A

10 mV/A

1 mA /A

10 mV/A

1 mV/A

Batttery, battery life

Output cable (m)

2.5

1.5

2.0

1.5

2.5

Shrouded banana plugs

BNC connector

BNC to banana adapter included

Safety

CAT III, 600V

CAT III. 600V

CAT III, 600V

CAT III 1000V /

CAT IV 600V

CAT III 1000V /

CAT IV 600V

i800

i1000s

i2000 flex

i3000s flex-24

i3000s flex-36

i3000s

i6000 flex-24

i6000s flex-36

Nominal current range(s)

800 A RMS

10 A

100 A

1000 A

20 A

200 A

2000 A

30 A

300 A

3000 A

30 A

300 A

3000 A

60 A

600 A

6000 A AC

Continuous AC current range

0.1 A - 800 A RMS

0.1 A - 10 A

0.1 A - 100 A

1 A - 1000 A

1 A - 20 A

2 A - 200 A AC RMS

30 A - 2000 A

1 A - 30 A

2 A - 300 A AC RMS

30 A - 3000 A

1 A - 30 A

1 A - 300 A

1 A - 2400 A

1 A - 6000 A AC RMS

Highest current

1500 A

2000 A

2500 A AC RMS

3500 A AC RMS

4000 A

6000 A

Lowest measurable current

0.1 A

0.1 A

1 A

1 A

1 A

1 A

Basic accuracy (48-65 Hz)

1)

0.10%

1% + 1 A

1%

1%

2% + 2 A

± 1% of range

Useable frequency

30 Hz - 10 kHz

5 Hz - 100 kHz

10 Hz - 20 kHz (-3dB)

10 Hz - 50 kHz (-3dB)

10 Hz - 100 kHz

10 Hz to 50 kHz

Max. working voltage

600V AC RMS or DC

600V AC

600V AC RMS

600V AC RMS

600V AC

600V AC RMS or DC

Maximum conductor diameter

54 mm

54 mm

178 mm

Flex-24 178 mm

Flex-36 275 mm

64 mm

Flex-24 170 mm

Flex-36 275 mm

Output level(s)

1 mA/A

100 mV/A

10 mV/A

1 mV/A

100 mV/A

10 mV/A

1 mV/A

100 mV/A

10 mV/A

1 mV/A

10 mV/A

1 mV/A

0.1 mV/A

50 mV/A

5 mV/A

0.5 mV/A

Batttery, battery life

200 hours

400 hours

400 hours

Output cable (m)

1.6

1.6

0.5

0.5

2.1

0.5

Shrouded banana plugs

n/a

BNC connector

n/a

BNC to banana adapter included

n/a

Safety

CAT III, 600V

CAT III, 600V

CAT III, 600V

CAT III, 600V

CAT III, 600V

CAT III, 600V

i5s

i200

i200s

i400

i400s

i800

i1000s

i2000 flex

i3000s flex

i3000s

i6000s flex

Specifications AC models

1)

Basic Accuracy: % reading + floorspec

1)

Basic Accuracy: % reading + floorspec