53
1555/1550C
Insulation Resistance Testers
The 1555 and redesigned Fluke 1550C
insulation resistance testers offer digital
insulation testing up to 10kV, making
them ideal for testing a wide range
of high voltage equipment including
switchgear, motors, generators and
cables. Fluke insulation testers can now
conduct the entire range of test voltages
specified in IEEE 43-2000 with a best
in class, 3-year warranty and CAT IV
600 V safety rating. With measurement
storage and PC interface, the 1555 and
1550C are perfect tools for preventative
or predictive maintenance programs
designed to identify potential equipment
failures before they occur.
• Test voltages up to 10 kV (1555)
provides solutions for all applications
• CAT III 1000 V, CAT IV 600 V safety rating
• Voltage breakdown detection alerts the
user that voltage is present and gives
the voltage reading up to 600 V AC or
DC for increased user safety
Fluke 1555
Fluke 1550C
Included accessories
Test Cables with Alligator Clips (red, black, green)
Infrared adapter with interface cable
FlukeView Forms Basic CD-ROM
AC Power Cord
Soft Carrying Case (base models only)
English Manual
Users Manual on CD-ROM
Quick Reference Card
Software License Agreement
Registration Card
FlukeView Forms Installation Guide
USB-IR Cable Installation Guide
IP67 Hard Case (kit only)
Certificate of Calibration (kit only)
Ruggedized Alligator Clips (kit and 1555 only)
Software specifications
Fluke ViewForms basic software requires a
PC running Windows 2000, Windows XP and
Windows Vista.
Optional Accessories
TL1550EXT 25 Foot Extended Test Lead Set
Ordering information
Fluke 1550C 5 kV
Insulation Tester
Fluke 1555 10 kV
Insulation Tester
Fluke 1550C/Kit 5 kV Insulation Tester Kit
Fluke 1555/Kit 10 kV Insulation Tester Kit
Test voltage (dc)
Range
Accuracy (± reading)
250 V
< 200 kΩ
200 kΩ to 5 GΩ
5 GΩ to 50 GΩ
> 50 GΩ
unspecified
5 %
20 %
unspecified
500 V
< 200 kΩ
200 kΩ to 10 GΩ
10 GΩ to 100 GΩ
> 100 GΩ
unspecified
5 %
20 %
unspecified
1000 V
< 200 kΩ
200 kΩ to 20 GΩ
20 GΩ to 200 GΩ
> 200 GΩ
unspecified
5 %
20 %
unspecified
2500 V
< 200 kΩ
200 kΩ to 50 GΩ
50 GΩ to 500 GΩ
> 500 GΩ
unspecified
5 %
20 %
unspecified
5000 V
< 200 kΩ
200 kΩ to 100 GΩ
100 GΩ to 1 TΩ
> 1 TΩ
unspecified
5 %
20 %
unspecified
10000 V (1555 only)
< 200 kΩ
200 kΩ to 200 GΩ
200 GΩ to 2 TΩ
> 2 TΩ
unspecified
5 %
20 %
unspecified
Bar Graph Range
0 to 1 TΩ & 0 to 2 TΩ (1555 only)
Insulation test voltage accuracy
-0 %, +10 % at 1 mA load current
Induced AC mains current rejection
2 mA maximum
Charging rate for capacitive load
5 seconds per μF
Discharge rate for capacitive load
1,5 s/μF
Range
Accuracy
Leakage current measurement
1 nA to 2 mA
± (5% + 2 nA)
Capacitance measurement
0,01 uF to 15,00 μF
± (15% rdg + 0,03 μF)
Timer
Range
Resolution
0 to 99 minutes
Setting: 1 minute
Indication: 1 second
Live circuit warning
Warning range
Voltage accuracy
30 V to 660 V AC/DC, 50/60 Hz
± (15% + 2 V)
Specifications
(Check the Fluke web for detailed specifications)
• Selectable test voltages in 50 V steps
from 250 to 1000 V, and 100 V steps
above 1000 V
• Measurements can be stored in up to 99
memory locations, with each location
assigned a unique, user defined, label
for easy recall
• Long battery life gives the user over 750
tests between charges
• Automatic calculation of Dielectric
Absorption (DAR) and Polarization
Index (PI) with no additional setup
• Guard system eliminates the effect
of surface leakage current on high-
resistance measurements
• Large digital/analog LCD for easy
viewing
• Capacitance and leakage current
measurement
• Ramp function for breakdown testing
• Resistance measurements up to 2TΩ
• Timer settings up to 99 minutes for
timed tests
• 3-year warranty
Digital insulation testing up to 10kV
Temperature (operating):
-20 °C to 50 °C
Temperature (storage):
-20 °C to 65 °C
Humidity:
80 % to 31 ºC decreasing linearly to
50 % at 50 ºC
Enclosure sealing:
IP40
Altitude:
0 to 2000 m
Power:
12 V lead-acid rechargeable battery,
Yuasa NP2.8-12
Dimensions:
170 mm x 242 mm x 330 mm
Weight:
3,6 kg
3-year warranty