Background Image
Previous Page  44 / 164 Next Page
Information
Show Menu
Previous Page 44 / 164 Next Page
Page Background

40

360 Leakage Clamp Meter

Included accessories

Test leads, temperature probe (Fluke 902),

soft carrying pouch and users manual

Ordering information

Fluke 360

Leakage Clamp Meter

Fluke 902 True-rms HVAC Clamp Meter

Features

• Measurement of leakage protectives

conductor and touch current with a

resolution of 1μA

• Advanced shielding to ensure accurate

results when measuring near other

conductors

• Automatic ranging within the manually

selected mA or A range

• Easily viewed measurements on digital

and bargraph display and HOLD when

measuring in hard to see locations

• Broad range of measurements currents

up to 60 A for all installation needs

• Easy carrying, pocket sized clamp with

wide 40 mm jaw size

• Display-Hold for convenience in use

• Auto power off with audible warning

buzzer

• Conformance to IEC61010 and EMC

standard

• Meets all the applications and

performance classes in safety standard

VDE0404-4 and the new VDE0702

leakage

current 0.5mA

ground

Specifications

Fluke 360

Functions

Range

Resolution

Accuracy

Current AC

3mA

30mA

0.001A

0.01mA

1% ± 5 counts

30A

60A

0.01A

0.1A

1% ± 5 counts (0~50A)

5% ± 5 counts (50~60A)

Frequency

50 and 60Hz

(Check the Fluke web for detailed specifications)

leakage current

1.2mA (e.g. via

motor shaft)

display: 1.7mA

Leakage current measurements with a tough,

pocket sized clamp meter

902 True-rms HVAC Clamp Meter

HVAC (heating, ventilation, air

conditioning) technicians require a service

tool that can consistently keep up with

their demands. The Fluke 902 expands the

existing line of quality Fluke clamp meters

by delivering the features necessary

to diagnose and repair HVAC systems.

Combined with true-rms technology

and a CAT III 600 V rating, the Fluke 902

helps technicians do their jobs safely and

accurately.

• Designed for HVAC applications with

capacitance, dc current (μA), and

temperature measurements

• Small body and jaws fit perfectly in your

hand and into tight places

• Handy “Display Hold” button keeps

measurements on the display

• Meter controls are positioned so current

measurements can be done with one

hand (index finger on clamp opening

lever and thumb on rotary switch)

• Three-year warranty

See specifications chart on page 34

Just for our HVAC pros

True RMS

Functions

Range

902

Current AC

0 to 600.0 A

2% ± 5 counts

Current DC

0 to 200.0 μA

1% ± 5 counts

Voltage AC

0 to 600.0 V

1% ± 5 counts

Voltage DC

0 to 600.0 V

1% ± 5 counts

Resistance range

0 to 9999 Ω

Jaw opening

30.5 mm

Max. wire size

750 MCM

Fluke 902

Specifications