89
CV Series ClirVu
®
IR Windows
Ordering Information
Fluke-CV200 50mm IR Window, hand turn
door latch
Fluke-CV201 50mm IR Window, security turn
door latch
Fluke-CV300 75mm IR Window, hand turn
door latch
Fluke-CV301 75mm IR Window, security turn
door latch
Fluke-CV400 95mm IR Window, hand turn
door latch
Fluke-CV401 95mm IR Window, security turn
door latch
Increase the safety and speed of your electrical
thermal imaging inspections with the new
Fluke ClirVu
®
infrared windows. Reduce the
risk of arc-flash and electrocution, increase the
safety of your personnel and reduce the time
and cost of preventive maintenance.
Features:
• Save time with quick and easy
installation - 5 minutes or less
- One technician
- One hole with standard Greenlee
®
punch
- Panel door does not need to be removed
- Grounds instantly to metal enclosure with
patent-pending AutoGround™ process
- Maintains panel arc test ratings up to 63kA
when properly installed
Compliance without compromise.
Safety without sacrifice: Your results matter
• Torture Tested™ to the highest arc blast test
ratings
- IEEE C37.20.7: 63 kA Arc tested at KEMA,
UL50/50E/50V, UL1558, IEC60529-1: IP67,
IEC 60068, NEMA 4/12, CSA C22.2 NO. 14-
13:2012, and CE
• Convenience of both quick turn or security
keyed access
• Fluke IR Windows offered in three sizes
50 mm, 75 mm and 95 mm (2 in, 3 in and 4 in)
• Work permit requirements and NFPA 70E
processes are significantly reduced
• Full PPE is often not required so inspections
are done faster and more comfortable
Specifications
Model
CV400
CV401
CV300
CV301
CV200
CV201
Size
95 mm
75 mm
50 mm
General
Voltage Range
Any
NEMA Environment Type
Type 4/12 (indoor/outdoor)
AutoGround™
Yes
ClirVu
®
Optic
Yes
Operating temperature
-40 ºC to + 232 ºC and + 260ºC Intermittent
Body material
EZAC & ZA-27 HIGH STRENGTH ZINC/ ALUMINUM ALLOY
Ratings and testing
Arc-Tested (IEEE C37.20.7)
63 kA for 30 cycles @ 60Hz at KEMA
UL 50V component
recognition
Yes
UL 50/NEMA Environmental
Rating
NEMA Type 4/12
UL 1558
Yes
CSA C22.2 No.
Yes
CSA Type Rating
Type 4
IP rating
IP67 at TUV
Lloyds Register
Up to 11 kV marine switchgear, indoor or outdoor (offshore only)
Vibration rating
IEC60068-2-6 at TUV
Humidity rating
IEC60068-2-3 at TUV
Install
Actual mounting hole
diameter required
115.42 mm
89.89 mm
61.37 mm
Greenlee Punch Kit =
Punch/Die
742BB = 2984AV/2983AV 739BB = 1431AV/1432AV 76BB = 441AV/442AV
Door Latch
Hand Turn Security
Key
Hand Turn Security
Key
Hand Turn Security
Key
Optics
Optic insert diameter
95 mm
95 mm
50 mm
Warranty
Lifetime replacement against manufacturing defects
Fluke CV400