VR1710 Single-Phase Voltage

Quality Recorder

The Fluke VR1710 is a single-phase, plug-

in voltage quality recorder that provides

fast and easy recording of voltage trends,

dropouts, harmonics and general power

quality including dips and surges to help

maintenance and facilities management

personnel easily pinpoint the root cause

of voltage problems. Voltage quality

parameters including RMS average,

transients, flicker, and harmonics up to

the 32nd are recorded using a user-

selected average period from

1 second to 20 minutes.

• Clear graphical summary of data and

quick overview of key power quality

parameters

• Get the complete picture with Min, Max,

Average RMS values (1/4 cycle) with

time stamps

• See the detailed with actual transient

display (> 100 μs) with time stamp

• Comprehensive analysis of Individual

harmonic and THD values with trends

Specifications

(Check the Fluke web for detailed specifications)

Display:

LED

Size (HxWxD):

23 x 19.75 x 22.2 cm

Included Accessories

Plug-in Fluke VR1710, USB cable, PowerLog

software CD, universal power cord adapters.

Ordering Information

Fluke VR1710

Voltage Quality Recorder

Fluke VR1710

Includes PowerLog software

Fluke VR1710 and included accessories

PowerLog Setup –

Simple set up of

internal clock, logging periods, and

intervals with default values for

quick results.

PowerLog View –

Data presentation

showing RMS voltage and harmonic

trends, actual transients, summary

information and statistics in

accordance with EN50160.

Actual transient display

(> 100 μs) with time stamp–

Quickly identify issues with included

graphical software.

Statistical analysis of voltage event

reduces analysis time by tracking

event quantities and magnitudes.

Applications

Voltage recording

– Monitors and

records supply voltage; measures RMS

average, minimum and maximum

values, and checks whether the socket

outlet is providing voltage within

tolerance.

Distortion measurement

– Measure

frequency and harmonics; check

whether the distorting loads (UPS

systems, drives, etc.) are affecting your

other equipment.

Flicker measurement

– Quantify the

affects of switching loads on lighting

systems.

Voltage transients

– Capture those

intermittent, momentary events that

may be affecting your equipment; the

full waveform is captured with date,

timestamp, and duration.

Weight:

0.8 kg

Two years warranty

Operating voltage

70V to 300V

Min/Max/Avg RMS value

Resolution 0.125V

Number of events

175,000

Dips/Interruptions

Yes

Time resolution

5 ms

Voltage resolution)

0.125V

Over-voltages

Yes

Frequency

Yes

Harmonics measurement

EN 61000-4-7 (up to 32nd)

Flicker measurement

EN 61000-4-15

Number of recording channels

1 Phase to Neutral

2 Phase/Neutral to Ground

Recording time

1 day to 339 days depending on average time from 1 second to 20 minutes

Transients

Yes (> 100μs)

Frequency range

50 Hz ± 1 Hz and 60 Hz ± 1 Hz

Safety category rating

CAT II 300V